The installation and operating instructions in this manual must be followed when installing and operating the
TP1 condensate pump. Please read them carefully. We recommend that you keep it close to the pump.
Particular attention must be paid to notes marked as follows:
WARNING
Other relevant regulations must also be observed, e.g. accident prevention regulations or internal operating
and safety instructions of the system manufacturer. Failure to follow these instructions can result in the loss of
all entitlement to claim damages.
2
INCLUDED ITEMS (Figure 1)
3
GENERAL DESCRIPTION
The TP1 condensate pump is an automatic pump for pumping condensation water from condensing boilers, air
conditioning systems, coolers, dehumidifiers or other similar systems. The corresponding regulations on
draining to the sewage system must be observed. If necessary, a neutralising unit must be installed upstream.
The TP1 condensate pump is not suitable for applications that involve the flow of large quantities of water (e.g.
swimming pools).
WARNING
DIMENSIONS (Figure 2)
4
5
SPECIFICATIONS
Supply voltage
−
Frequency
−
Input power
−
Current consumption
−
Degree of protection
−
Insulation class
−
Max. delivery head
−
Max. pump capacity
−
Noise level (L
w
−
Acid resistance
−
Max. media temperature
−
Min. ambient temperature
−
Floating contact
−
Tank volume
−
Packaging dimensions
−
Packaging weight
−
CURVE (figure 3)
6
7
INSTALLATION SEQUENCE (figure 4)
8
If this instruction is not followed, personal safety risks could ensue.
If this instruction is not followed, the device may not function properly and could be
damaged.
Combustible liquids may not be pumped!
The condensate pump may not be run dry, as this can destroy the bearings in a very
short period.
)
100 - 240 V
50 / 60 Hz
25 W
0.2 – 0.1 A
IP 44
Class 155 (F)
52 kPa (5.3 m H
O)
2
350 l/h
46 dB(A)
pH 2 or higher
+60 °C
not freezing
alarm relay NC 250 V AC, 3 A
0.7 l (usable volume 0.5 l)
215 x 215 x 180 mm
1.6 kg