ASTRALPOOLHEAT SERIES · AIR/WATER SYSTEM

4 START-UP OF THE HEAT PUMP

4.1 Installation Rules

It is necessary to determine the unit location according to certain criteria:
· The unit must be secured on a hard base (concrete or hard steel frame type) and must be protected from flood risks.
· The unit must be installed outside, taking advantage of the sun's direct rays.
· A clear space around the unit of around 23,5'' (0.6 meters) at the front, adequate room for serviceability, and a
minimum of 20'' (0.5 meters) at the back and sides of the unit must be left.
· If the heat pump is to be installed in a garage or under a vertical overhang, the unit must have a minimum of 106'' (2.5
meters) clearance from the top of the heat pump.
· The air caused by the helix must be directed away from the limits of the work environment (windows, doors...).
· The minimum distance between the heat pump and the rim of the swimming pool must be at least 127'' (3.5 meters).
(Electrotechnic Regulations for Low Voltage, Supplementary Technical Instructions, Low Voltage, 31, ITC-BT-31).
· The electrical and hydraulic connections must be made according to the applicable regulations (NF C 15 100, EC 1
364). The ducting for the connections must be fixed.
During operation of the unit, it is normal that the condensation produced by the evaporation unit will produce a certain
quantity of water which will have to be evacuated. The units have a 0.47'' (12 mm) diameter barbed adapter for the
200/275 models and a 0.75'' (19 mm) diameter barbed adapter for the 400/550/650 models at the side of the base
which should always be free of any obstruction.
 It is important to remember that no part of the tubing or hose may be above the level of the drain hole in the base of the
heat pump.
 This condensation water does not have to be treated in any special manner.
Keep lawn sprinkler heads from spraying on the heat pump to prevent corrosion and damage. Use a deflector if
needed.
 Make sure the heat pump is not located where large amounts of water may run off from a roof into the unit. Sharp
sloping roofs without gutters will allow massive amounts of rain water, mixed with debris from the roof, to be forced
through the unit.

4.2 Hydraulic Connections

Remove the seals from the three piece connections of the water intake of the pool. Connect the PVC 50 piping water inlets
and outlets of the swimming pool to the heat pump inlet and outlet. The connection will be performed through a by-pass over
the filtering circuit of the swimming pool after the filter and before the water treatment. Adjust the flow so that the arrow of
this pressure gauge in the green zone.
DOSER OR
CHLORINATOR
CHECK VALVE
© ASTRALPOOL 2008. ALL RIGHTS RESERVED. CONFIDENTIAL AND PROPRIETARY DOCUMENT.
ASTRALPOOLHEAT
BY-PASS

Figure 1: Hydraulic connections.

FILTER
FILTRATION PUMP
ENGLISH