1.4 Think of your safety
If you smell gas, it is expressly prohibited:
– To ignite an appliance
– To touch electrical switches, or to telephone from the area in question
Take the following action:
– Switch off the gas and electricity
– Activate the operational emergency plan
– Evacuate the building if necessary

2.0 Installation

2.1 Positioning the appliance
After unpacking, check the unit for damage. Check the accuracy of the type/model and the
electrical voltage. Place the appliance and any accessories on a sufficiently solid structure [2 & 3],
taking into account the minimum free space required [1]. Use the M10 suspension points for this.
Note in particular the space needed for cleaning the burner and flue gas fan.
2.2 Positioning the flue gas exhaust system and air supply
C32 Flue gas exhaust system
The maximum length L [3] of the intake and flue pipe is six metres incl. 2x2 90° bends (3xD).
Each additional right-angled bend shortens the length by 2 metres. If possible, use bends of 45°.
The maximum length for type 104 is 1 metre, incl. 1x2 90° bends. Different flue plans are possible
on request.
C12 Flue gas exhaust system
A bend may, if required, be located directly on the appliance. The maximum length L [3] of the
intake and flue pipe is six metres incl. 2x2 90° bends. Each additional right-angled bend shortens
the length by 2 metres. If possible, use bends of 45°. The maximum length for type 104 is 1 metre,
incl. 1x2 90° bends. Different flue plans are possible on request. The flue gas exhaust system should
be installed with a minimum of a 3° pitch from the appliance. [3]
Position the system and attach it i correctly according to the flue gas exhaust system installation
instructions. If the flue gas exhaust system is shorter than 3 metres (L<3m), fit the restriction ring
supplied. See table [3] for the correct diameter and fitting.
The appliance only has CE approval if the roof or wall pass-through supplied by the manufacturer is
used. This may be supplied by the manufacturer under the following part numbers:
Device type
18 to 49
55 to 104
The extension pipes and bends of the gas flue exhaust system must meet the following
requirements:
Device type
18 to 49
55 to 104
Roof pass-through C32
59 90 556
59 90 560
Nominal diameter
80mm
100mm
Wall pass-through C12
59 90 579
59 90 583
EN
5