Air filter
If an air filter is fitted, a dirty filter sensor should always be fitted.
1.4 Think of your safety
If you smell gas, it is expressly prohibited:
– To ignite an appliance
– To touch electrical switches, or to telephone from the area in question
Take the following action:
– Switch off the gas and electricity
– Activate the operational emergency plan
– Evacuate the building if necessary

2.0 Installation

2.1 Positioning the appliance
After unpacking, check the unit for damage. Check the accuracy of the type/model and the
electrical voltage. Place the appliance and any accessories on a sufficiently solid structure [2 & 3],
taking into account the minimum free space required [1]. Use the M10 suspension points for this.
Note in particular the space needed for cleaning the burner and flue gas fan.
Note: the heat exchanger's maximum temperature is approximately 500 °C. The appliance may be
installed in an area where the ambient temperature lies between -10°C and 40 °C.
2.2 Positioning the flue gas exhaust system and air supply
C32 Flue gas exhaust system
The maximum length L [3] of the intake and flue pipe is six metres incl. 2x2 90° bends (3xD).
Each additional right-angled bend shortens the length by 2 metres. If possible, use bends of 45°.
The maximum length for type 95 is 1 metre, incl. 1x2 90° bends. Different flue plans are possible
on request.
C12 Flue gas exhaust system
A bend may, if required, be located directly on the appliance. The maximum length L [3] of the
intake and flue pipe is six metres incl. 2x2 90° bends. Each additional right-angled bend shortens
the length by 2 metres. If possible, use bends of 45°. The maximum length for type 95 is 1 metre,
incl. 1x2 90° bends. Different flue plans are possible on request. The flue gas exhaust system
should be installed with a minimum of a 3° pitch from the appliance. [3]
Put the flue gas system into position and attach it correctly according to the installation
instructions for the flue gas discharge system. Ensure that connections to the appliance are
properly tightened. Use the restrictor provided if the flue gas discharge system is less than 3
metres in length (L<3m), . See table [3] for the correct diameter and position.
The appliance only has CE approval if the roof or wall pass-through supplied by the manufacturer
is used. This may be supplied by the manufacturer under the following part numbers:
Device type
20 to 45
50 to 95
Roof pass-through C32
59 90 556
59 90 560
Wall pass-through C12
59 90 579
59 90 583
EN
5